logo

Stairways

A stairway should be of sufficient width for the number of people who are likely to use it in an emergency and it should not normally be less than 1 metre wide. However, a narrower one may be adequate if you are sure that only a few people, who are familiar with the stairway, will use it. Where more than one stairway is provided, you should assume that the widest one may be unusable as a result of the fire. This means that the remaining stairway(s) will need to provide a satisfactory escape route for everyone present.

There may be no need for you to discount the widest stairway where each stairway is reached through a protected lobby. Certain other compensatory features, such as sprinklers or smoke control systems, may also be considered. Stairways should normally be protected by fire-resisting partitions and fire-resisting, self-closing doors (except toilet doors) and lead directly to a way out of the building. An unprotected stairway may, however, be suitable in workplaces of low or normal fire risk, provided that:

  • the stairway links no more than two floors and those floors are not linked to another floor by an unprotected stairway; and
  • it is additional to that required for escape purposes; and
  • no escape route from a dead-end situation on an upper floor passes the access to such a stairway.

People should not have to pass through a protected stairway to reach an alternative stairway. Where this cannot be achieved, a stairway may be by-passed, for instance by using doors connecting adjacent rooms. In such situations the doors should be kept free from obstruction and available for use at all times. A single stairway may be suitable for means of escape in workplaces of low or normal fire risk, provided that people on each floor can reach it within the appropriate travel time (see details of distances earlier in this section).

It also needs to:

  • be constructed as a protected stairway and serve no more than three floors above, or one floor below, ground level;
  • be accessed, other than at the top floor, by means of a protected lobby or protected corridor;
  • be of sufficient width to accommodate the number of people who may need to use it in an emergency; and
  • lead direct to open air.

There is no need for you to provide protected lobbies where the workplace is of low fire risk. This also applies to workplaces of normal fire risk, provided that either an automatic fire detection system or sprinklers linked directly into the fire alarm system are installed in the rooms or areas leading directly onto the protected stairway. In small workplaces of low or normal fire risk, unprotected stairways (including a single stairway) may be satisfactory as a means of escape, provided that:

  • the stairway provides access between the ground and first floor and/or ground floor and basement only, and an exit can be reached from any part of those floors within the escape times given for single escape routes earlier in this section; and
  • access to the stairway is clearly visible from any part of the floor it serves and it exits not more than 6 metres from a storey exit leading direct to open air at ground level.

    Where an external stairway is provided, any door or window (other than toilet windows) opening onto the stairway, or within 1.8 metres horizontally or 9 metres vertically of it, should be fire-resisting. Windows should be unopenable and doors should be self-closing. In exceptional circumstances, a small number of unprotected, openable windows may be allowed, provided that the rooms containing them are separated from the rest of the building by fire-resisting construction and the external stairway is not the only one from the upper storeys.

    Accommodation stairways

    Your workplace may have stairways that are not needed as part of the formal means of escape.

    These stairways are known as accommodation stairs and will not need to be protected, provided that:

    • they do not serve protected corridors;
    • they do not link more than two floors; and
    • people do not have to move towards the head of an unprotected stairway to make their escape.

    Means of escape for use by staff

The features listed below are not normally acceptable as a means of escape for members of the public as they are not conventional escape routes. However, they may, in certain circumstances, be used by a small number of staff if they are trained to do so or use the exit during their normal work activity:

  • revolving doors (except those specifically designed for escape purposes);
  • portable, foldaway, vertical-raking or throw-out ladders;
  • window exits;
  • wicket doors and gates;
  • wall and floor hatches; and
  • rolling shutters and folding, sliding or up-and-over doors.

Lifts should not be used as a means of escape, but see 'Use of lifts as means of escape' on page 70 for details on the evacuation of disabled staff.



» How to contact us » Fire risk assessments » FREE fire extinguisher training » Fire safety products
» Risk assessment example » Knowledge base » FREE site sign surveys » Fire extinguisher training
» 5 steps of risk assessments » Risk assessment in depth » Extinguisher guidance chart » Home Fire safety pack
» What is the fire safety order? » Fire extinguisher servicing » Fire extinguisher sales » Fire escape signs
» Assessment steps in depth » P.A.T testing » Fire warden training » Risk assessment guides
» Sharing energency plans » Firework safety info » Fire safety records » Escape routes capacities
» Advice Mobility impaired » Fire escape routes guidance » Firefighters switches guidance » Foam inlets guidance
» Suppression systems » Schematic plans guidance » Voice alarms guidance » Dry & wet rising mains
» Fire detection & warning » People with special needs » Arson » Fire-resisting structures
» Catering facilities guidance » Display materials & decorations » Insulated core panels » Hazards/corridor escape routes